10kva Online Ups With Isolation Transformer 220v
- MAXI
- GUANGDONG
- ≤100 units 20 days
- 2000 units per month
10kva Online Ups With Isolation Transformer
TXF 10KVA UPS contraposes all types of computers and sophisticated electronic equipment needs,aims fine quality, excellent functionality and capacity operation to design.It maintains the traditional advantages of online machine, improving protection circuit, IGBT drivers balance, high-frequency charging performance
1.Stable performance for advanced digital circuit system.
2.With internal transformer, ensuring input/output isolate completely
3.Transfer time 0ms, no interruption from AC state to DC state
4.Intelligent battery charger, durable and worry-saving
5.Perfect protection function, short circuit, over load, over temp, battery high/low protection
6.Direct LCD data display work status
7.Communication interface RS232,remote control SNMP card is optional
MODEL | 10K-ISO TX | ||
CAPACITY | VA/W | 10000VA/9000W | |
INPUT | Input isolation transformer | connected on input end | |
Voltage Range | 120~264VAC(120±5~274±5)VAC | ||
Frequency Range | default 50Hz (46Hz-54Hz)/default 60Hz (56Hz-64Hz) | ||
Phase | Single Phase with Ground | ||
Power Factor | ≥0.96 | ||
OUTPUT
| Voltage | 220/230/240VAC | |
Voltage Regulation | ±1% | ||
Frequency(Synchronized Range) | 47Hz-53Hz/57Hz-63Hz) | ||
Frequency (BAT Mode) | 50/60Hz±0.2Hz | ||
Current Crest Ratio | 3:1 | ||
Harmonic Distortion | <3% THD(Linear Load) | ||
<5% THD(Non-Linear Load ) | |||
Output Waveform | Pure Sine Wave | ||
Overload Capacity | Line Mode | Overload warning only,105%±5%≤load 40S,then transfer to bypass and alarm,105%±5%<load≤120%±5% 100ms,then transfer to bypass and alarm,load>120%±5% | |
EFFICIENCY | Line Mode | >88% | |
BAT Mode | >85.0%(91%) | ||
ECO Mode | >87.7%(91%) | ||
BATTERY | Number of Batteries | 16 | |
Battery Type | 12V/9AH | ||
Backup Time (Full Load) | >2 minutes | ||
Recharge Time | 7 hours to 90% | ||
Charging Current | 1.5A(1A) | ||
TRANSFER TIME | BAT <--> LINE | 0ms | |
INV <--> BYPASS | <4ms | ||
INV-->ECO | <4(10)ms | ||
ECO--> INV | <10ms | ||
INDICATOR | LCD | Load/Battery/Input/Output/Operating Mode Information | |
AUDIBLE ALARM | BAT Mode | beeps every 4 seconds | |
Battery Low | beeps every second | ||
Fault | Continuously beeping | ||
Overload Capacity | beeps twice every second | ||
MECHANICAL | Dimension:WxDxH(mm) | 260x540x720 | |
Net Weight (Kg) | 93 | ||
ENVIRONMENT | Operation Environment | 0-40℃ | |
Relative Humidity | 0-95% (Non-Condensing) | ||
Noise Level | <54dB @ Front 1 meter | ||
INTERFACE | USB/RS232 | Software supports Windows Family, Linux, Sun Solaris, IBM Aix, Compaq True64, SGIIRIX, FreeBSD, HP-UX, MAC | |
External Slot | Optional, External Type of SNMP/AS400 Card | ||
EPO | Emergency Power Off |