UPS BATTERY 12V 17AH FEATURES:
Long service life
1.Variety of rare earth element has been added to the internal grids, which will result in a 25% rise in service life. The enhanced grid will become somewhat immune to corrosion.
2.Green and environment protection
3.The laminated sealing tech will 100% insulate acid leakage of batteries and effectively prevent the acid fog from polluting environment.
1. High Rate Discharge Valve Regulated Lead-Acid 12V/17AH External Storage Battery
2. Storage VRLA Battery LC-R1217, 12V/17AH
3. Large surface area active material, a lower internal resistance, suitable for high current discharge applications, can provide high power output in a short time
4. compared with normal cells, can be output in a short time more than 25% of the power, the Storage Battery design life of 3 years
Battery Type | LC-R1117, 12V/17AH | |||
(25 ℃) Design Life | 3 Years | |||
(25 ℃) Capacity | 20HR(0.85A,1.75V) | 10HR(1.7A,1.8V) | 1C(17A,1.6V) | 3C(51A,1.6V) |
18.0AH | 15.0AH | 10.0AH | 6.5AH | |
Dimension | Lenght | Width | Height | Total Height |
181.5±1mm(7.15inch) | 76.5±1mm(3.01inch) | 167±1mm(6.58inch) | 167±1mm(6.58inch) | |
Weight | 5.4 Kg (11.91lbs) | |||
(25 ℃)Internal Resistance | ≤13.5 mΩ Charging Saturation Status | |||
(25 ℃)Self-discharge | About 3% / Month | |||
(20HR)Capacity While Various Temperature | 40 ℃ | 25 ℃ | 0 ℃ | -15 ℃ |
102% | 100% | 85% | 65% | |
Complementary Charging System | Cycling Use | Standby Use | ||
14.4~15.0V(-30mv/℃),3.6 A Max initial current | 13.6~13.8V(-20mv/℃) |