MXD33 10KVA Feature:
High quality and availability of energy adapted to suit specific critical needs, covering a vast range of applications,it provides protection for networking sector, security applications (electro medical) and industrial applications.
1.LCD display:Alpha-Numeric Display which displays system parameters and alarms.
2.Audible alarms:Provides notification of changing utility power and UPS power conditions
3.LED status indicators:Quickly understand unit and power status with visual indicators.
4.Automatic internal bypass:Supplies utility power to the connected loads in the event of a UPS power overload or fault.
5.Network manageable:Provides remote power management of the UPS over the network.
MODEL | MXD 10KVA | ||
Input Mains | Rated voltage(V) | 380Vac 3phase+N | |
Rated voltage&Range(v) | 380V±25% | ||
Frequency&Range(Hz) | 50/60Hz±4Hz | ||
Bypass Input | Rated voltage(V) | 380V(Line Voltage) | |
Rated voltage&Range(v) | 380V±25% | ||
Frequency&Range(Hz) | 50/60Hz±4Hz | ||
Output | Rated Power | 10K/9KW | |
Rated Voltage(V) | 380V(Line Voltage) | ||
Rated Voltage&Stability | 380V±2% | ||
THDV | Linear Load | ≤3% | |
Non-linear Load | ≤8% | ||
Output Power factor | 0.9 | ||
Tracking Frequency&Range(Hz) | 50/60Hz±4Hz | ||
Frequency&Stability (Battery Inverter) | (50/60±0.1)Hz | ||
Overload Capability | Less than 105%±5% for overload alarm;105%±5%~125%±5% for 2 minutes 125%±5%~150%±5% for 30second; more than 150%±5% for 0.5 second | ||
Converting time (Normal Mode) | <4ms | ||
Converting time(ECO Mode) | <25ms | ||
System Efficiency (Linear Load) | ≥80 ≥76 | ||
System Efficiency (ECO Mode) | ≥96% | ||
Physical | W*D*H (mm) | 455*830*1055 | |
N.W. (kg) | 200 | ||
System | Display | LED/LCD | |
EMS/EMI | Transmission | IEC 62040-02 | |
Radiation | IEC 62040-02 | ||
Resisting Interference | IEC 61000-4-4.2.5 Level IV, IEC 61000-4-3 Level III | ||
Safety Requirements | GB4943-2001/IEC62040-1 | ||
Noise Level(1M) | ≤55dB | ||
Isolate Impedance(Ω) | >2M(500VDC) | ||
Surge Current Protection | IEC60664-1 IV | ||
Environment | Operating Temperatures | 0~40 | |
Elevation | <1000m | ||
Storing Temperatures | -15~45 | ||
Operation Humidity | 20%~95% | ||
Battery | 192VDC |