100 kva 3 phase online ups price
- MAXI
- GUANGDONG
- ≤100 units 20 days
- 1000 units per month
MX 33 100KVA Feature:
MX 33 100KVA UPS is a three-phase, double conversion uninterruptible power supply (UPS).Its design fits perfectly to any environment where uninterrupted power feed is required to secure critical equipment’s continuous operation. The MX 33 100KVA UPS provides a perfect solution for power protection, and solves power quality problems such as surges, spikes, voltage fluctuations, harmonic distortion, clutter interference and frequency fluctuations.
1. Pluggable power module design with front access to decrease MTTR, parallel redundancy capability for power guarantee
2.Parallel operation with common battery
3.Power walk-in function
4.Dual-mains inputs
5.Built-in 4 switches including Main input,bypass input ,output and maintenance bypass swtich
6.Flexible battery configuration and adjustable charging current
7.Output power factor 1
8.Active power factor correction in all phases
9.Built-in 7"touch LCD screen for comprehensive information
10.Emergency power off function(EPO)
11.Generator compatible
12.50Hz/60Hz frequency converter mode
MODEL | 100K |
PHASE | 3-phase in/3-phase out |
CABINET CAPACITY | 100KVA/100KW |
BATTERY TYPE | External Battery |
PARALLEL CAPABILTY | 4 |
INPUT | |
Nominal Voltage | 3*380/400/415 VAC(3Ph+N) |
Voltage Range | 110-300VAC@50% load;176-276 VAC@100% load |
Nominal Frequency | 50/60Hz(Auto sensing) |
Frequency Range | 40Hz-70Hz |
Power Factor | ≥0.99@100% load |
Hamonic Distortion(THDi) | <4% at full linear load |
OUTPUT | |
Nominal Voltage | 3*380/400/415 VAC(3Ph+N) |
Voltage Regulation(Steady state) | ≤±1% Typical (balanced load) ≤±2% Typical(unbalanced load) |
Nominal Frquency | 50/60Hz |
Frequency Range(Synchronized range) | 46Hz~54Hz or 56Hz~64Hz |
Overload Capability | ≤110% for 1 hour,111%~125% for 10mins,126%~150% for 1 min and >150% for 200ms |
Hamonic Distortion | ≤2% THD(Linear Load);≤4%THD (Non-linear Load) |
EFFICIENCY | |
AC Mode | 95.5% |
ECO Mode | 98.5% |
Battery Mode | 94.5% |
BYPASS | |
Nominal Voltage | 3*380/400/415 VAC(3Ph+N) |
Voltage Range | -30%~+20% |
Frequency Range | 46Hz~54Hz or 56Hz~64Hz |
Overload Capability | ≤110% for 1 hour,111%~125% for 10mins,126%~150% for 1 min and >150% for 200ms |
BATTERY/CHARGER | |
Nominal Voltage | +/- 192V~+/- 240v(Selectable) |
Maximum Voltage | +/-240V(12v*40Pcs) |
Minimum Voltage | +/-240V(12v*32Pcs) |
Floating Charging Voltage | 2.28V/Cell(2.25~2.33 Selectable) |
Boost Charging Voltage | 2.35V/Cell |
Temperature Compensation | Yes |
Maximum Charging Current(Per Power Module) | 24A(Adjustable) |
PHYSICAL | |
IP Class | IP20 |
Dimension,D*W*H(mm) | 1000*430*1200 |
Net Weight(Kgs) | 200 |
ENVIRONMENT | |
Operating Temperature | 0-40℃ |
Operating Humidity | <95% and non-condensing |
Altitude | <1000m for Nominal power |
MANAGEMENT | |
Smart RS-232/USB | Supports Windows Family ,Linux and MAC |
Optional SNMP | Power management from SNMP manager and web browser |
STANDARDS | |
Safety | IEC/EN 62040-1 |
EMC | IEC/EN 62040-2 Category C3 |