Pure Sine Wave Ups 30kva 3 Phase For Server
- MAXI
- GUANGDONG
- ≤100 units 25 days
- 200 units per month
MXD31 30KVA Feature:
1. High level battery reliability:
- Automatic battery test
- Battery care, Battery life span can be increased approximately by 20% more
2. Back feed protection: to avoid energy feeding back into the mains supply
3. Bypass may be deactivated to allow operation as a frequency converter (at 50 or 60 Hz), or as stabilizer
4. Easy to maintain (front access)
5. Reliable, filtered, stabilised and regulated sine wave output (double on-line concersion technology VFI according to EN50091-3 specifications) with filters for atmospheric disturbance suppression
6. High reliability: IGBT technology, full microprocessor control with no-break static and manual bypass
7. High level diagnostics: event log with 128 messages, states, measurements and alarms-available from the built-in LCD in several languages
8. The UPS may be configured with the RS232 serial port (flash up-gradable )
1.Adopt the latest three-level inverter technology
2.Advanced DSP digital control system
3.Active input Power Factor Correction (PFC)
4.Super wide input frequency range
5.Output power factor 0.8
6.Powerful expansibility features
MODEL | MXD 30K | |||
Input Mains | Rated voltage(V) | 380Vac 3phase+N | ||
Rated voltage&Range(v) | 380V±25% | |||
Frequency&Range(Hz) | 50/60Hz±4Hz | |||
Bypass Input | Rated voltage(V) | 220V/230V | ||
Rated voltage&Range(v) | 380V±25% | |||
Frequency&Range(Hz) | 50/60Hz±4Hz | |||
Output | Rated Power | 30KVA/24KW | ||
Rated Voltage(V) | 220V/230V | |||
Rated Voltage&Stability | 220V/230V±2% | |||
THDV | Linear Load | ≤3% | ||
Non-linear Load | ≤8% | |||
Output Power factor | 0.8 | |||
Tracking Frequency&Range(Hz) | 50/60Hz±4Hz | |||
Frequency&Stability (Battery Inverter) | (50/60+0.1)Hz | |||
Overload Capability | Less than 105%±5% for overload alarm;105%±5%~125%±5% for 2 minutes 125%±5%~150%±5% for 30 second; more than 150%±5% for 0.5 second | |||
Converting time (Normal Mode) | <1ms | |||
Converting time(ECO Mode) | <25ms | |||
System Efficiency(Linear Load) | ≥85 | |||
System Efficiency(ECO Mode) | ≥96% | |||
Physical | W*D*H (mm) | 455*830*1055 | ||
N.W. (kg) | 178 | |||
System | Display | LCD/LED | ||
EMS/EMI | Transmission | IEC 62040-02 | ||
Radiation | IEC 62040-02 | |||
Resisting Interference | IEC 61000-4-2.4.5 Level IV, IEC 61000-4-3 Level III | |||
Safety Requirements | GB4943-2001/IEC62040-1 | |||
Noise Level(1M) | ≤55dB | |||
Isolate Impedance(Ω) | >2M(500VDC) | |||
Surge Current Protection | IEC60664-1 IV | |||
Environment | Operating Temperatures | 0℃~40℃ | ||
Elevation | <1000m | |||
Storing Temperatures | -15℃~45℃ | |||
Operation Humidity | 20%~95% | |||
Battery voltage | 384VDC |