Low Frequency Online Ups 6kva For Telecom
- MAXI
- GUANGDONG
- ≤100 units 25 days
- 800 units per month
MXD 11 6KVA Feature:
Continuous on-line, double-conversion operation provides precise voltage regulation and sine wave output. It isolates connected equipment from most power problems, including blackouts, brownouts, overvoltages, transient voltage surges, harmonic distortion, electrical impulses and frequency variations.
1.True on-line, double-conversion operation
2.Expandable battery backup supports critical systems during outages
3.LCD/LED control panel displays power conditions and permits easy access to settings
4.Network card slot supports optional remote access and network management
5.USB ports connect to computers for power management
Index | MXD11 6K | Comments |
Input | ||
Input voltage | ||
Rated voltage | 220VAC | |
Phase | Single phase with ground | |
Turn on voltage range | 220±25% VAC | |
Bypass voltage range | 220VAC±25% | Phase voltage; Could be adjusted by software.
|
Bypass low loss | 165VAC | |
Bypass low comeback | Low loss +10VAC | |
Bypass high loss | 275VAC | |
Bypass high comeback | High loss-10VAC | |
Line low loss/comeback | (165±5) VAC /(180±5) VAC | |
Line high loss/comeback | (275±5)VAC/(260±5)VAC | |
Input frequency | ||
Rated frequency | 50Hz | Could be adjusted by software. |
Frequency low loss | (40~49)±0.2Hz(default:46Hz) | |
Frequency low comeback | Frequency low loss + 0.5Hz | |
Frequency high loss | (51~60)±0.2Hz(default:54Hz) | |
Frequency high comeback | Frequency high loss - 0.5Hz | |
Input power factor | ||
Input power factor | Max 0.8 | |
Generator | Support generator input | Generator rating≥2*UPS rating |
Input current | ||
Rated current | 61A | |
Input protection | ||
Rated protection | 80A | |
Output | ||
Output power | ||
VA/watt | 6KVA/4.8KW | |
Rated voltage | 220VAC | Sine wave |
Phase | Single phase with ground | |
Voltage range | 200/208/220/230/240VAC | Could be adjusted by software. 10% derating for 208VAC/200VAC. |
Voltage regulation | ±2% | |
Voltage distortion | ≤8% | Full RCD load |
≤3% | Full R load |
Index | MXD11 6K | Comments | |||
DC offset | ≤200mV | ||||
Transient response | ≤9% | R load 0%~100%~0% | |||
≤6% | R load 20%~100%~20% | ||||
Transient recovery | ≤60ms voltage recovery to 90% | Full RCD load | |||
Bypass output before turn-on | Yes | ||||
Crest ration | 3:1 | ||||
Output frequency range | |||||
Line mode | 1.Same as input frequency(46Hz~54Hz) | ||||
2.50Hz(Input frequency>54Hz or Input frequency<46Hz) | |||||
Battery mode | (50+0.1) Hz | ||||
Slew rate | 1 Hz/Sec | ||||
Efficiency | |||||
Line mode | > 80% | R load | |||
Battery mode | > 85% | R load | |||
Overload | |||||
line mode/battery mode | Overload warning only | 105%±5%≤load | |||
2Min,then transfer to bypass and alarm. | 105%±5%<load≤125%±5% | ||||
30S,then transfer to bypass and alarm. | 125%±5%<load≤150%±5% | ||||
0.5S,then transfer to bypass and alarm. | load>150%±5% | ||||
Automatically recovery | Yes | ||||
Short protection | |||||
Line/battery mode | Cut off output and alarm after 3S | ||||
Transfer time | |||||
Line to battery mode | 0mS | ||||
Battery to line mode | 0mS | ||||
Line to bypass mode | <1mS | ||||
Bypass to line mode | <1mS | ||||
Battery and charger | |||||
Battery | |||||
Rated voltage | 192VDC |
Index | MXD11 6K | Comments |
Protection | ||
Low alarm voltage / comeback voltage | (180.8V±4V)/ (188.8V±4V) | |
Shutdown voltage | (176V±4V)/ (184V±4V) | Watt Value < 1000W |
(160V±4V)/ (168V±4V) | Watt Value ≥ 1000W | |
Battery protection | ||
Overcharge protection | (250V±4V) | |
Battery test | ||
Battery weak | Support | |
Battery fault | Support | |
Charger | ||
Output voltage | (220±2)VDC | Float charge voltage |
Charge time | Determined by battery capacity | |
Charge current | 7A | |
Interface | ||
Alarm silence | Support | |
DC power turn-on | Support | |
Automatically restart | Support | |
alarm | ||
Battery mode | Beep/4s | |
Battery low/charger fault | Beep/1s | |
UPS fault | Continuously beep | |
Overload | Beep/1s | |
Bypass mode | Beep/2Min | |
Communication | ||
RS232/ RS485 interface | Support | |
Output dry contactor | Support | |
Intelligent slot | Support | |
Monitor software | Appending with UPS | |
Cooling | ||
Force air cooling | ||
Display | ||
LCD displays UPS status | Support |