MXD 11 2KVA Description
MXD 11 2KVA UPS is single phase in & single phase out . Due to its prominent industrial and electronic design, the UPS not only could work safe in the harsh environment, but also could provide maximum protection office automation, network, security applications and industrial applications.
Single phase in, single phase out
Microprocessor control
True on-line double conversion design
Sine wave pulse width modulation
Wide Input voltage windows
Index | MXD11 2kVA | Comments |
Input | ||
Input voltage | ||
Rated voltage | 220VAC | |
Phase | Single phase with ground | |
Turn on voltage range | 220±25% VAC | |
Bypass voltage range | 220VAC±25% | Phase voltage; Could be adjusted by software.
|
Bypass low loss | 165VAC | |
Bypass low comeback | Low loss +10VAC | |
Bypass high loss | 275VAC | |
Bypass high comeback | High loss-10VAC | |
Line low loss/comeback | (165±5) VAC /(180±5) VAC | |
Line high loss/comeback | (275±5)VAC/(260±5)VAC | |
Input frequency | ||
Rated frequency | 50Hz | Could be adjusted by software. |
Frequency low loss | (40~49)±0.2Hz(default:46Hz) | |
Frequency low comeback | Frequency low loss + 0.5Hz | |
Frequency high loss | (51~60)±0.2Hz(default:54Hz) | |
Frequency high comeback | Frequency high loss - 0.5Hz | |
Input power factor | ||
Input power factor | Max 0.8 | |
Generator | Support generator input | Generator rating≥2*UPS rating |
Input current | ||
Rated current | 24A | |
Input protection | ||
Rated protection | 32A | |
Output | ||
Output power | ||
VA/watt | 2KVA/1.6kW | |
Rated voltage | 220VAC | Sine wave |
Phase | Single phase with ground | |
Voltage range | 200/208/220/230/240VAC | Could be adjusted by software. 10% derating for 208VAC/200VAC. |
Voltage regulation | ±2% | |
Voltage distortion | ≤8% | Full RCD load |
≤3% | Full R load |
Index | MXD11 2kVA | Comments | ||
DC offset | ≤200mV | |||
Transient response | ≤9% | R load 0%~100%~0% | ||
≤6% | R load 20%~100%~20% | |||
Transient recovery | ≤60ms voltage recovery to 90% | Full RCD load | ||
Bypass output before turn-on | Yes | |||
Crest ration | 3:1 | |||
Output frequency range | ||||
Line mode | 1.Same as input frequency(46Hz~54Hz) | |||
2.50Hz(Input frequency>54Hz or Input frequency<46Hz) | ||||
Battery mode | (50+0.1) Hz | |||
Slew rate | 1 Hz/Sec | |||
Efficiency | ||||
Line mode | > 80% | R load | ||
Battery mode | > 85% | R load | ||
Overload | ||||
line mode/battery mode | Overload warning only | 105%±5%≤load | ||
2Min,then transfer to bypass and alarm. | 105%±5%<load≤125%±5% | |||
30S,then transfer to bypass and alarm. | 125%±5%<load≤150%±5% | |||
0.5S,then transfer to bypass and alarm. | load>150%±5% | |||
Automatically recovery | Yes | |||
Short protection | ||||
Line/battery mode | Cut off output and alarm after 3S | |||
Transfer time | ||||
Line to battery mode | 0mS | |||
Battery to line mode | 0mS | |||
Line to bypass mode | <4mS | |||
Bypass to line mode | <4mS | |||
Battery and charger | ||||
Battery | ||||
Rated voltage | 192VDC |
Index | MXD11 2kVA | Comments |
Protection | ||
Low alarm voltage / comeback voltage | (180.8V±4V)/ (188.8V±4V) | |
Shutdown voltage | (176V±4V)/ (184V±4V) | Watt Value < 1000W |
(160V±4V)/ (168V±4V) | Watt Value ≥ 1000W | |
Battery protection | ||
Overcharge protection | (250V±4V) | |
Battery test | ||
Battery weak | Support | |
Battery fault | Support | |
Charger | ||
Output voltage | (220±2)VDC | Float charge voltage |
Charge time | Determined by battery capacity | |
Charging current | 1.2A/5A | |
Interface | ||
Alarm silence | Support | |
DC power turn-on | Support | |
Automatically restart | Support | |
alarm | ||
Battery mode | Beep/4s | |
Battery low/charger fault | Beep/1s | |
UPS fault | Continuously beep | |
Overload | Beep/1s | |
Bypass mode | Beep/2Min | |
Communication | ||
RS232/ RS485 interface | Support | |
Output dry contactor | Support | |
Intelligent slot | Support | |
Monitor software | Appending with UPS | |
Cooling | ||
Force air cooling | ||
Display | ||
LCD displays UPS status | Support |
Index | MXD11 2KVA | Comments |
Environment | ||
Work temperature | 0℃~40℃ | |
Altitude | <1000m | |
Audible noise | ≤55dB | |
Storage temperature | -15℃~45℃ | |
Work humidity | 20%~95% | |
Standard | ||
EMS/EMI | ||
Conducted | IEC62040-02 | |
Radiated | ||
Anti-interference | IEC 61000-4-2.4.5 Level IV, IEC61000-4-3 Level III | |
Safety | ||
Safety | GB4943-2001/IEC62040-1 | |
Transportation | ||
Drop test | GB-T4857-18 | |
Vibration test | B-WR1-129(GB-T14715-93) | |
Machinery features | ||
Connection | ||
Inlet | Wiring terminal block | |
Outlet | Wiring terminal block | |
External battery slot | Wiring terminal block | |
Size | ||
N.W. and size | ||
L*W*H(mm) | 560*260*717 | |
N.W.(Kg) | 37/104 | |
G.W. and package size | ||
L*W*H(mm) | 630*320*865 | |
weight(Kg) | 42/112 | |
Optional functions | ||
60Hz | Support | Could be set by software |
Converter mode | Support | Could be set by software |
ECO mode | Support | Could be set by software |
EPO mode | Support | Need to increase related components |